Loading…
Name ID Label Description Type Access Class
vol_flow_analog_value 404E Volume Flow mA Value R/W Float 66
vol_flow_analog_upper_limit 404F Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
vol_flow_analog_lower_limit 4050 Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
vol_flow_additional_analog_damping 4051 Added Damping Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
vol_flow_percent_range 4052 Volume Flow Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
vol_flow_upper_range_value 4053 Volume Flow Upper Range Value Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_lower_range_value 4054 Volume Flow Lower Range Value Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_upper_sensor_limit 404C Volume Flow Upper Sensor Limit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
vol_flow_lower_sensor_limit 4055 Volume Flow Lower Sensor Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
vol_flow_minimum_span 4056 Volume Flow Minimum Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
Name ID Label Description Type Access Class