Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
flow_pres_factor | 4188 | Flow Pressure Factor | Pressure compensation factor applied to flow rate (% change per PSI). | R/W | Float | 8 |
dens_pres_factor | 4189 | Density Pressure Factor | Pressure compensation factor applied to density (g/Cucm change per PSI). | R/W | Float | 8 |
zero_pres_factor | 418A | Flow Calibration Pressure | Pressure at which flow calibration was performed. | R/W | Float | 8 |
enable_pres_comp | 41D2 | Pressure Compensation | This parameter allows you to enable/disable the pressure correction feature | R/W | Enum | 8 |
static_pressure | 41D3 | Compensation Pressure | This parameter allows you to enter a static pressure when using the pressure correction feature | R/W | Float | 8 |
enable_extern_temp | 41E4 | External Temperature | This parameter allows you to enable/disable the external temperature feature | R/W | Enum | 8 |
static_temperature | 41E5 | Correction Temperature | This parameter allows you to enter a static temperature when using the external temperature feature | R/W | Float | 8 |
flow_switch_setpoint | 418B | Setpoint | This parameter can be used to trigger a discrete output when the mass flow rate exceeds the configured setpoint. There is a fixed hysteresis of 5% for this setpoint. | R/W | Float | 16 |
do1_assignment | 418C | Assignment | This parameter identifies which condition the discrete output will act upon. | R/W | Enum | 1024 |
do1_state | 41CD | Discrete Output State | This parameter identifies the state of the discrete output. | R/W | Enum | 2 |
Name | ID | Label | Description | Type | Access | Class |