Name ID Label Description Type Access Class
flow_pres_factor 4188 Flow Pressure Factor Pressure compensation factor applied to flow rate (% change per PSI). R/W Float 8
dens_pres_factor 4189 Density Pressure Factor Pressure compensation factor applied to density (g/Cucm change per PSI). R/W Float 8
zero_pres_factor 418A Flow Calibration Pressure Pressure at which flow calibration was performed. R/W Float 8
enable_pres_comp 41D2 Pressure Compensation This parameter allows you to enable/disable the pressure correction feature R/W Enum 8
static_pressure 41D3 Compensation Pressure This parameter allows you to enter a static pressure when using the pressure correction feature R/W Float 8
enable_extern_temp 41E4 External Temperature This parameter allows you to enable/disable the external temperature feature R/W Enum 8
static_temperature 41E5 Correction Temperature This parameter allows you to enter a static temperature when using the external temperature feature R/W Float 8
flow_switch_setpoint 418B Setpoint This parameter can be used to trigger a discrete output when the mass flow rate exceeds the configured setpoint. There is a fixed hysteresis of 5% for this setpoint. R/W Float 16
do1_assignment 418C Assignment This parameter identifies which condition the discrete output will act upon. R/W Enum 1024
do1_state 41CD Discrete Output State This parameter identifies the state of the discrete output. R/W Enum 2
Name ID Label Description Type Access Class