Name ID Label Description Type Access Class
drive_lower_range_value 4191 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
drive_upper_sensor_limit 41B0 USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
drive_lower_sensor_limit 41B1 LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
drive_minimum_span 41B2 Min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
api_dens_digital_value 41D4 TC Dens R Float 10
api_dens_analog_value 41E2 TC Dens R/W Float 66
api_vol_flow_digital_value 41D5 TC Vol R Float 10
api_vol_flow_analog_value 41E3 TC Vol R/W Float 66
api_vtot_digital_value 41D6 TC Vol totl R Float 10
api_vinv_digital_value 41D7 TC Vol inv R Float 10
Name ID Label Description Type Access Class