Loading…
Name ID Label Description Type Access Class
flow_tgco 407D FTG This parameter represents the Flow Temperature Gradient Coefficient (FTG) that is on the T-series sensor tag. R/W Float 8
flow_fqco 407E FFQ This parameter represents the Flow Frequency Coefficient (FFQ) that is on the T-series sensor tag. R/W Float 8
max_zero 407F Zero time The number of readings collected from the sensor during an Auto Zero operation. R/W Unsigned 4
pulse_width 4080 Max pulse width A programmable time period, in seconds, that defines the crossover frequency for the frequency output, where Crossover freq. = 1 / (2 x Pulse width). Below the crossover, the output has a constant ON state, and an OFF state that varies with frequency. R/W Float 512
tempcal 4081 Temp cal factr A 14-character factor that describes the slope and offset of the linear output representing flow tube temperature. R/W ASCII 32
rt_zero 4082 ゼロ A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R/W Float 2
zero_offset_units 4083 Zero units Units for zero offset - always microseconds. R/W Unsigned 32
rt_sigma 4084 Std dev A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. R Float 2
fault_index 4085 Output Type R/W Index 4096
LMV_fault_timeout 4087 Fault Timeout This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. R/W Unsigned 4
Name ID Label Description Type Access Class