Loading…
Name ID Label Description Type Access Class
sp_volume_time 4073 Base vol time A standard unit of time (seconds, minutes, hours, or days) that serves as the time component in a special unit. R/W Enum 32
sp_volume_fact 4074 Vol flo conv factr A programmable multiplier for the base volume unit in a special unit. R/W Float 32
sp_volume_rate_text 4075 Vol flo text A 1 to 8 character description of a special unit of flow. R/W ASCII 2048
sp_volume_total_text 4076 Vol totl text A 1 to 8 character description of a special unit of volume, which is based on the special unit of flow to represent total. R/W ASCII 2048
fixfreq 4077 固定周波数 A value (in Hertz) that will be indicated on the frequency output for the purpose of a loop test. R/W Float 4096
totctl 4078 積算計コントロール Allows the user to Reset, Stop, or Start all totalizers. NOTE - Inventory totals are NOT reset. R/W Enum 4096
fo_scaling_method 401B FO Scale Method This parameter allows you to scale the frequency output by using freq=flow, pulses/unit, or units/pulse. This parameter must be sent to the device before you make scaling changes. R/W Enum 512
dens_tgco 407A DTG This parameter represents the Density Temperature Gradient Coefficient (DTG) that is on the T-series sensor tag. R/W Float 8
dens_fqco1 407B DFQ1 This parameter represents the Density Frequency Coefficient #1 (DFQ1) that is on the T-series sensor tag. R/W Float 8
dens_fqco2 407C DFQ2 This parameter represents the Density Frequency Coefficient #2 (DFQ2) that is on the T-series sensor tag. R/W Float 8
Name ID Label Description Type Access Class