Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sp_volume_rate_text | 4075 | Vol flo text | A 1 to 8 character description of a special unit of flow. | R/W | ASCII | 2048 |
sp_volume_total_text | 4076 | Vol totl text | A 1 to 8 character description of a special unit of volume, which is based on the special unit of flow to represent total. | R/W | ASCII | 2048 |
fixfreq | 4077 | Фикс. част | A value (in Hertz) that will be indicated on the frequency output for the purpose of a loop test. | R/W | Float | 4096 |
totctl | 4078 | Управление сумматором | Allows the user to Reset, Stop, or Start all totalizers. NOTE - Inventory totals are NOT reset. | R/W | Enum | 4096 |
fo_scaling_method | 401B | FO Scale Method | This parameter allows you to scale the frequency output by using freq=flow, pulses/unit, or units/pulse. This parameter must be sent to the device before you make scaling changes. | R/W | Enum | 512 |
dens_tgco | 407A | DTG | This parameter represents the Density Temperature Gradient Coefficient (DTG) that is on the T-series sensor tag. | R/W | Float | 8 |
dens_fqco1 | 407B | DFQ1 | This parameter represents the Density Frequency Coefficient #1 (DFQ1) that is on the T-series sensor tag. | R/W | Float | 8 |
dens_fqco2 | 407C | DFQ2 | This parameter represents the Density Frequency Coefficient #2 (DFQ2) that is on the T-series sensor tag. | R/W | Float | 8 |
flow_tgco | 407D | FTG | This parameter represents the Flow Temperature Gradient Coefficient (FTG) that is on the T-series sensor tag. | R/W | Float | 8 |
flow_fqco | 407E | FFQ | This parameter represents the Flow Frequency Coefficient (FFQ) that is on the T-series sensor tag. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |