Loading…
Name ID Label Description Type Access Class
temp_lower_range_value_1 403E Temp LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
temp_upper_sensor_limit 403F Temperature Upper Sensor Limit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
temp_digital_damping 4040 Temperature Damping Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 32
temp_lower_sensor_limit 4041 Temperature Lower Sensor Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
temp_minimum_span 4042 Temperature Minimum Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
mtot_digital_units 4046 Mass totl unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R Enum 32
mtot_digital_value 4047 Mass Total R Float 10
dens_digital_units 404A Density Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R/W Enum 32
dens_digital_value 404B Density R Float 10
dens_digital_cutoff 404D Density Cutoff The density below which the density indicates zero. R/W Float 8
Name ID Label Description Type Access Class