Loading…
Name ID Label Description Type Access Class
do1_state 41D1 DO is This parameter identifies the state of the discrete output. R/W Enum 1024
do_index 41D2 DO index R/W Index 4096
mass_flow_digital_units 4005 Mass flo unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R/W Enum 32
mass_flow_digital_value 4007 Mass flo R Float 2
mass_flow_digital_cutoff 4009 Mass flo cutoff The mass flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. R/W Float 8
mass_flow_analog_value 400A Mass flo anlog valu R/W Float 66
mass_flow_analog_upper_limit 400B Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
mass_flow_analog_lower_limit 400C Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
mass_flow_additional_analog_damping 400D Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
mass_flow_percent_range 400E Mass flo % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
Name ID Label Description Type Access Class