Name ID Label Description Type Access Class
update_rate 40FB Update Rate This parameter is the update rate for process variables through the system. Set the update rate to NORMAL for most applications. Set the update rate to SPECIAL if you are using the device in proving applications or extremely short batch applications. Refer to the user's manual for more information before you change this parameter. R/W Enum 2048
update_rate_var 40FC Update rate var This parameter identifies the transmitter variable that will be updated at 100 Hz. All others will be updated, but at a slower rate. R/W Enum 2048
flow_pres_factor 40FD Flow factr Pressure compensation factor applied to flow rate (% change per PSI). R/W Float 8
dens_pres_factor 40FE Dens factr Pressure compensation factor applied to density (g/Cucm change per PSI). R/W Float 8
zero_pres_factor 40FF Flowcal pressure Pressure at which flow calibration was performed. R/W Float 8
flow_switch_setpoint 4100 Flow Switch Setpoint This parameter can be used to trigger a discrete output when the mass flow rate exceeds the configured setpoint. There is a fixed hysteresis of 5% for this setpoint. R/W Float 16
unique_device_type_code 07ED R/W Enum 4096
rosemount_model_code 07F5 R/W Enum 4096
rosemount_analytical_model_code 07F6 R/W Enum 4096
kayray_model_code 07F7 R/W Enum 4096
Name ID Label Description Type Access Class