名称 ID 标签 描述 类型 访问 分类
fault_index 4060 Output Type 读/写 索引 4096
ao_1_fault_code 46E3 故障动作 Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. 读/写 枚举 12
ao_2_fault_code 46E9 故障动作 Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. 读/写 枚举 12
dig_comm_fault_code 46FB 故障动作 This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) 读/写 枚举 12
discrete_output_fault_code 46FC Fault Action This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) 读/写 枚举 12
ao_1_fault_level 46E4 故障等级 This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 3.2 to 3.6 mA for downscale or 21.0 to 21.5 for upscale. 读/写 浮点 64
ao_2_fault_level 46EA 故障等级 This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 3.2 to 3.6 mA for downscale or 21.0 to 21.5 for upscale. 读/写 浮点 64
LMV_fault_timeout 4064 Fault Timeout This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. 读/写 无符号 12
history_0 4A3B Alarm Event Log Index 无符号 2048
history_1 4A3C Alarm Event Log Index 无符号 2048