Name ID Label Description Type Access Class
dp_minimum_span 4075 Pressure Minimum Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
alarm_1_digital_value 4077 Event 1 R Float 2
alarm_1_digital_units 4078 Event1 unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 32
alarm_1_analog_value 4079 Event1 Analog Value R/W Float 66
alarm_1_analog_upper_limit 407A Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 66
alarm_1_analog_lower_limit 407B Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 66
alarm_1_percent_range 407C Event1 Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
alarm_1_upper_range_value 407D Event 1 Upper Range Value Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
alarm_1_lower_range_value 407E Event 1 Lower Range Value Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
alarm_1_analog_value_1 41B8 Event1 Analog Value R/W Float 66
Name ID Label Description Type Access Class