Name ID Label Description Type Access Class
mmi_flow_upper_sensor_limit 4008 Flo URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
mmi_flow_lower_sensor_limit 4011 Flo LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
mmi_flow_minimum_span 4012 Flo min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
temp_digital_units 4018 Temp unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 32
temp_digital_value 4019 Temp R Float 2
temp_analog_value 401A Temp anlog valu R/W Float 66
temp_percent_range 401B Temp % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
temp_upper_range_value 401C Temp URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
temp_lower_range_value 401D Temp LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
temp_upper_sensor_limit 401E Temp URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8