Loading…
Loading…
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
fo_fault_code | 40DC | 故障动作 | Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. | 读/写 | 枚举 | 12 |
dig_comm_fault_code | 40DE | 故障动作 | This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) | 读/写 | 枚举 | 12 |
ao_1_fault_level | 40DA | 故障等级 | This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. | 读/写 | 浮点 | 64 |
fo_fault_level | 40DD | 故障等级 | This parameter allows you to select the upper frequency output level that will indicate a fault condition. The maximum value is 15000 Hz. | 读/写 | 浮点 | 64 |
density_for_cal | 40E0 | 读/写 | 浮点 | 4096 | ||
point_code | 40E1 | 读/写 | 无符号 | 4096 | ||
densityfd_for_cal | 40E2 | 读/写 | 浮点 | 4096 | ||
temp_for_cal | 40E3 | Ref temperature | User-entered temperature for the purpose of performing an on-line temperature calibration. | 读/写 | 浮点 | 4096 |
cutoff_code | 40E6 | 切除类型 | 读/写 | 索引 | 4096 | |
D1 | 40E7 | D1 | The density, in g/cc, of the air or other low-density fluid used during a 2-point density calibration. | 读/写 | 浮点 | 8 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |