名称 ID 标签 描述 类型 访问 分类
fo_fault_code 40DC 故障动作 Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. 读/写 枚举 12
dig_comm_fault_code 40DE 故障动作 This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) 读/写 枚举 12
ao_1_fault_level 40DA 故障等级 This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. 读/写 浮点 64
fo_fault_level 40DD 故障等级 This parameter allows you to select the upper frequency output level that will indicate a fault condition. The maximum value is 15000 Hz. 读/写 浮点 64
density_for_cal 40E0 读/写 浮点 4096
point_code 40E1 读/写 无符号 4096
densityfd_for_cal 40E2 读/写 浮点 4096
temp_for_cal 40E3 Ref temperature User-entered temperature for the purpose of performing an on-line temperature calibration. 读/写 浮点 4096
cutoff_code 40E6 切除类型 读/写 索引 4096
D1 40E7 D1 The density, in g/cc, of the air or other low-density fluid used during a 2-point density calibration. 读/写 浮点 8