名称 ID 标签 描述 类型 访问 分类
flow_tgco 40C9 FTG This parameter represents the Flow Temperature Gradient Coefficient (FTG) that is on the T-series sensor tag. 读/写 浮点 8
flow_fqco 40CA FFQ This parameter represents the Flow Frequency Coefficient (FFQ) that is on the T-series sensor tag. 读/写 浮点 8
max_zero 40CB Zero Time The amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds. 读/写 无符号 12
pulse_width 40CC Maximum Pulse Width A programmable time period, in seconds, that defines the crossover frequency for the frequency output, where Crossover freq. = 1 / (2 x Pulse width). Below the crossover, the output has a constant ON state, and an OFF state that varies with frequency. 读/写 浮点 512
tempcal 40CD Temperature Calibration Factor A 14-character factor that describes the slope and offset of the linear output representing flow tube temperature. 读/写 ASCII 32
rt_zero 40CE Zero Value A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. 读/写 浮点 10
rt_sigma 40CF Standard Deviation 标准偏差是从最后一次调零期间采集的调零样品数量获得的 2 西格玛级结果。“标准偏差”、“实时零点”、“智能零点校验”和“现场校验零点”可用于查看您仪表上的零点稳定程度。 浮点 10
fault_index 40D0 Output Type 读/写 索引 4096
LMV_fault_timeout 40D2 Fault Timeout This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. 读/写 无符号 12
ao_1_fault_code 40D8 故障动作 Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. 读/写 枚举 12