Loading…
Name ID Label Description Type Access Class
sp_volume_fact 40BF Conversion Factor A programmable divider for the base volume unit in a special unit. R/W Float 32
sp_volume_rate_text 40C0 Flow Label A 1 to 8 character description of a special unit of flow. R/W ASCII 2048
sp_volume_total_text 40C1 Total Label A 1 to 8 character description of a special unit of volume, which is based on the special unit of flow to represent total. R/W ASCII 2048
fixfreq 40C2 Fixed freq A value (in Hertz) that will be indicated on the frequency output for the purpose of a loop test. R/W Float 4096
totctl 40C3 Totlizer cntrl Allows the user to Reset, Stop, or Start all totalizers. NOTE - Inventory totals are NOT reset. R/W Enum 4096
fo_scaling_method 4021 Frequency Output Scaling Method This parameter allows you to scale the frequency output by using freq=flow, pulses/unit, or units/pulse. This parameter must be sent to the device before you make scaling changes. R/W Enum 512
fo_polarity 40C5 Polarity This parameter allows you to set the polarity of the frequency output. R/W Enum 512
dens_tgco 40C6 DTG This parameter represents the Density Temperature Gradient Coefficient (DTG) that is on the T-series sensor tag. R/W Float 8
dens_fqco1 40C7 DFQ1 This parameter represents the Density Frequency Coefficient #1 (DFQ1) that is on the T-series sensor tag. R/W Float 8
dens_fqco2 40C8 DFQ2 This parameter represents the Density Frequency Coefficient #2 (DFQ2) that is on the T-series sensor tag. R/W Float 8
Name ID Label Description Type Access Class