Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
live_zero_vol_flow_percent_range_1 | 42D2 | Volume Flow Percent Range | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
live_zero_vol_flow_upper_range_value_1 | 4169 | Mass Flow Upper Range Value | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
live_zero_vol_flow_lower_range_value_1 | 416A | Mass Flow Lower Range Value | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
live_zero_vol_flow_upper_sensor_limit | 42D3 | Mass Flow Upper Sensor Limit | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
live_zero_vol_flow_lower_sensor_limit | 42D4 | Mass Flow Lower Sensor Limit | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 8 |
live_zero_vol_flow_minimum_span | 42D5 | Mass Flow Minimum Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
live_zero_vol_flow_hzfreq | 4165 | Frequency Factor | The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. | R/W | Float | 512 |
live_zero_vol_flow_hzrate | 4166 | Rate Factor | The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. | R/W | Float | 512 |
live_zero_vol_flow_p_u | 4167 | Pulses/Unit | This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. | R/W | Float | 512 |
live_zero_vol_flow_u_p | 4168 | Units/Pulse | This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. | R/W | Float | 512 |
Name | ID | Label | Description | Type | Access | Class |