Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sp_mass_rate_text | 40B3 | Flow Label | A 1 to 8 character description of a special unit of flow. | R/W | ASCII | 2048 |
sp_mass_total_text | 40B4 | Total Label | A 1 to 8 character description of a special unit of mass, which is based on the special unit of flow to represent total. | R/W | ASCII | 2048 |
met_direct | 40B5 | Flow Direction | This parameter enables the user to determine whether the outputs and totalizers will indicate forward, reverse, bi-directional or absolute value flow. | R/W | Enum | 32 |
slughi | 40B6 | Slug High Limit | A programmable high limit on density, which enables the transmitter to indicate slug flow (extremes in fluid density caused by slugs of gas or accumulation of solids in a liquid flow stream) if fluid density goes outside programmed slug flow limits. | R/W | Float | 8 |
sluglo | 40B7 | Slug Low Limit | A programmable low limit on density, which enables the transmitter to indicate slug flow (extremes in fluid density caused by slugs of gas or accumulation of solids in a liquid flow stream) if fluid density goes outside programmed slug flow limits. | R/W | Float | 8 |
slug_duration | 40B8 | Slug Duration | A programmable time period, from 0.00 to 60.00 seconds, during which outputs representing flow hold their last measured value before indicating slug flow. | R/W | Float | 12 |
flocal | 40B9 | FlowCal | A 10-character factor that describes the sensitivity of the sensor to mass flow. The first 6 characters are the flow rate, in grams/second, per microsecond of time shift between velocity signals from the sensor. The 2nd four characters are the flow temperature coefficient. | R/W | ASCII | 32 |
fcf | 40BB | Flow FCF | A 10-character factor that describes the sensitivity of the sensor to mass flow. The first 6 characters are the flow rate, in grams/second, per microsecond of time shift between velocity signals from the sensor. The 2nd four characters are the flow temperature coefficient. | R/W | ASCII | 32 |
ma_1_cutoff | 4028 | mA Output Flow Rate Cutoff | The mass or volume flow rate below which a milliamp output representing flow indicates zero flow. | R/W | Float | 8 |
ma_2_cutoff | 40BC | SV AO cutoff | The mass or volume flow rate below which a milliamp output representing flow indicates zero flow. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |