Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
tube_amplitude_digital_units | 44EE | Left Pickoff Amplitude | The pickoff voltage of the sensor measured in Voltage. | R | Enum | 32 |
tube_amplitude_L | 40F7 | Left Pickoff Amplitude | R | Float | 10 | |
tube_amplitude_R | 40F8 | Right Pickoff Amplitude | R | Float | 10 | |
drive_gain | 40F9 | Drive Gain | The drive gain of the transmitter. | R | Float | 10 |
live_zero | 40FA | Live Zero Flow Rate | This flow value is not effected by the flow cutoff and is damped at 8 seconds. It is to be used for diagnostic purposes only and is not used in ANY flow calculations or totalization. | R | Float | 10 |
board_temp_700 | 40FB | Board Temperature | The board temperature of the core processor. | R | Float | 10 |
case_temp | 40FC | Meter Temperature (T-Series) | The meter temperature of the T-Series sensor. | R | Float | 10 |
Input_voltage | 40FD | Input Voltage | R | Float | 10 | |
Actual_Target_Amplitude | 40FE | Act Target Amplitude | Displays current target amplitude value. | R | Float | 10 |
Average_sensor_temp | 40FF | Avg Sensor Temp | R | Float | 10 | |
Name | ID | Label | Description | Type | Access | Class |