Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pg_arrow_down | 403A | ArrowDown | Transmitter arrow-down key state | R | Enum | 2 |
pg_pressure_percent_range | 4052 | % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 2 |
pg_pressure_alarm_code | 4051 | Alarm current | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 2048 |
pg_pressure_transfer_function | 4043 | Lin.func | Linearization Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Linearization Function affect the Digital Value representation only when using USER - User function linearization. | R/W | Enum | 2048 |
pg_pressure_range_units | 403D | Range unit | R | Enum | 2048 | |
pg_pressure_lower_range_value | 403E | LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Minimum for LRV is 10 % under Lower Sensor Limit | R/W | Float | 2048 |
pg_pressure_upper_range_value | 403F | URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Maximum for URV is 10 % over Upper Sensor Limit | R/W | Float | 2048 |
pg_pressure_damping_value | 4040 | Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 2048 |
pg_pressure_sensor_sn | 4053 | Sensor s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Integer | 2048 |
pg_pressure_sensor_units | 4045 | R | Enum | 2048 | ||
Name | ID | Label | Description | Type | Access | Class |