Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
loop_alarm_code | 00EC | AO Alarm Type | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
percentRange | 00E9 | Percent of Range | Porcentaje de rango: Variable que rastrea la representación del valor digital con respecto al rango definido por el valor de rango inferior y el valor de rango superior, para modos de funcionamiento normales. Las unidades de esta variable siempre son en porcentaje. | R | Float | 34 |
transfer_function | 1F84 | Transfer function | Función de transferencia: Define la función de transformación que se aplicará desde la variable de dispositivo de campo a la salida analógica y el rango de porcentaje. La función de transferencia no afecta a la representación del valor digital. | R/W | Enum | 32 |
upperRange_value | 00EA | Upper Range Value | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 32 |
lowerRange_value | 00EB | Lower Range Value | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 32 |
sensor_a_lower_sensor_trim_point | 1774 | Lower Trim Point | Lower Sensor Trim Point - The pressure at which the last low sensor trim was performed. | R/W | Float | 8 |
sensor_a_upper_sensor_trim_point | 1776 | Upper Trim Point | Upper Sensor Trim Point - The pressure at which the last upper sensor trim was performed. | R/W | Float | 8 |