Name ID Label Description Type Access Class
rIirFilterCoefficient 402E PV Damping Dampening factor to smooth fluctuations in flow rate. Enter value between 0.001 to 0.999 with 0.001 being most damping and 0.999 with no damping. R/W Float 8
rFlowCutoff 402F Low Flow Cutoff Flow measurements below this value will output a 4mA signal. R/W Float 8
rFlowMax 4030 Flow Max PV Upper Range Value or 20 mA value. R/W Float 8
rPulseCount 4031 Pulse Count Flow Units per pulse. R/W Float 8
cFloatVariablesArrayIndex 4032 R/W Index 4096
sRateString 4036 Flow Rate Units Text entry of desired units of measurement. If changed from default entry a correction factor must be entered under K Factor. R/W ASCII 2048
sTotalString 4037 Total Units Three digit text entry of desired units for the total flow. If changed from default entry this value will not be adjusted. Recommend no change to default conditions. Note fourth digit code for temperature units, F for Fahrenheit, C for Celsius R/W ASCII 2048
cASCIIArrayIndex 4038 R/W Index 4096
lFlowRateSerialNumber 403C Meter S/N Factory entry of the serial number of the instrument. R Unsigned 2048
lPulseDuration 403F Pulse Duration Selectable between 50 and 1000 ms. Default is 250 ms. W Integer 8