Name ID Label Description Type Access Class
device_specific_status_0_and_1 4000 Status R BitEnum 2051
pressure_value 138E Pres Primary Variable- Digital representation that tracks the Analog Output(if it exists) Number 1, under normal operating modes R/W Float 10
pressure_classification 4003 Pres class Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. R Enum 8
pressure_units 138D Pres unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 8
pressure_PDQ 4005 Pres PDQ Process Data Quality- Indicates the overall process data quality of the device variable value. R Enum 10
pressure_LS 4006 Pres LS Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). R Enum 10
pressure_status 4007 Pres Fmly stat Device Family Status- Indicates additional status information on a device variable for a specific device family. R BitEnum 10
pressure_upper_limit 4008 Pres USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
pressure_lower_limit 4009 Pres LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
pressure_minimum_span 1390 Pres min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
Name ID Label Description Type Access Class