Name ID Label Description Type Access Class
Analog_input2_PDQ 4044 PDQ Process Data Quality- Indicates the overall process data quality of the device variable value. R Enum 10
Analog_input2_LS 4045 LS Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). R Enum 10
Analog_input2_Status 4046 Family status Device Family Status- Indicates additional status information on a device variable for a specific device family. R BitEnum 10
Analog_input2_USL 4047 USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R/W Float 0
Analog_input2_LSL 4048 LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R/W Float 0
Analog_input2_MinimumSpan 4049 Minimum Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R/W Float 0
Analog_input2_DampingValue 404A Temp damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 0
Analog_input2_SerialNumber 404B Sensor s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
Analog_input2_Simulated 404C Simulate W Enum 2052
Analog_input2_UpdatePeriod_int 404D Temp Update Period R Unsigned 0