Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
eAlarm2Type | 402B | Alarm 2 Type | A latching alarm remains active after the alarm condition has cleared. A non-latching alarm will deactivate once the alarm condition has cleared. | R/W | Enum | 1024 |
eAlarm2State | 402C | Alarm 2 Condition | An energized alarm relay has the normally open and common connections shorted in a non-alarm condition. A de-energized alarm relay has the normally closed and common connections shorted in a non-alarm condition. | R/W | Enum | 1024 |
eAlarm3Direction | 402D | Alarm 3 Direction | An ascending alarm is activated when the concentration goes from below the alarm threshold to above it. A descending alarm is activated when the concentration goes from above the threshold to below it. Descending alarms are used for oxygen sensors. Ascending alarms are used for all other gases. | R/W | Enum | 1024 |
eAlarm3Type | 402E | Alarm 3 Type | A latching alarm remains active after the alarm condition has cleared. A non-latching alarm will deactivate once the alarm condition has cleared. | R/W | Enum | 1024 |
eAlarm3State | 402F | Alarm 3 Condition | An energized alarm relay has the normally open and common connections shorted in a non-alarm condition. A de-energized relay has the normally closed and common connections shorted in a non-alarm condition. | R/W | Enum | 1024 |
eFaultRelayType | 4030 | Fault Relay Type | A latched fault will remian active after the fault condition has cleared. A non-latched fault will clear once the fault condition has cleared. | R/W | Enum | 1024 |
eFaultRelayState | 4031 | Fault Relay Condition | An energized fault relay has the normally open and common connections shorted in a non-fault condition. A de-energized fault relay has the normally closed and common connections shorted in a non-fault condition. | R/W | Enum | 1024 |
uiSerialNumber | 405A | Serial Number | Serial number for the attached sensor | R | Unsigned | 2048 |
uiBridgeSetpoint | 404B | Bridge Setpoint | Target current for the sensor cell bridge circuit | R/W | Unsigned | 8 |
eSoftwareFilterMode | 4032 | Filter Mode | Enables software filtering of the sensor cell output | R/W | Enum | 8 |
Name | ID | Label | Description | Type | Access | Class |