Loading…
Name ID Label Description Type Access Class
eModelType 400F Model type The type of Detcon sensor that is connected to the Detcon HRT Bridge R Enum 2048
uiDaysSinceLastCal 4037 Days last cal Number of days that have elapsed since the last successful AutoSpan calibration R Unsigned 2048
eSensorRange 4024 Sensor Range The maximum value of the concentration that can be detected by the sensor R/W Enum 2048
eCellBias 4025 Cell Bias Voltage applied between the sensing and counter electrodes of an electrochemical cell R Enum 2048
uiGainCode 4038 Gain Code Value of the gain of the internal amplifier in the sensor cell R Unsigned 2048
uiRawCounts 4039 Raw Counts Numerical value measured by the analog-to-digital converter circuit R Unsigned 2048
uiGasFactor_2 403A Gas Factor Used to make the appropriate signal sensitivity adjustment when the target gas is other than methane R Unsigned 2048
uiCalFactor_2 403B Cal Factor Used to make the appropriate signal sensitivity adjustment when the calibration gas is other than methane R Unsigned 2048
uiBridgeCurrent 403C Bridge Current Current flowing through the bridge circuit of the sensor R Unsigned 2048
uiBridgeVoltage 403D Bridge Voltage Voltage applied to the bridge circuit of the sensor R Unsigned 2048
Name ID Label Description Type Access Class