Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
temp_sensor_status | 403C | Temp Sensor | Temp Sensor - Provides status of the Temperature sensor in the TA2. Will display either OK, Shorted, or Open. | R | Enum | 2050 |
flow_sensor_status | 403D | Flow Sensor | Flow Sensor - Provides status of the Flow sensor in the TA2. Will display either OK, Shorted, or Open. | R | Enum | 2050 |
probe_heater_status | 403E | Probe Heater | Probe Heater - Provides status of the Probe Heater in the TA2. Will display either OK, Shorted, or Open. | R | Enum | 2050 |
heater_setting | 403F | Heater Setting | Heater Setting - Displays a value for the heater setting. Useful for diagnostics information. | R | Integer | 2050 |
install_factor_A | 4021 | A | Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. | R/W | Float | 32 |
install_factor_B | 4023 | B | Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. | R/W | Float | 32 |
install_factor_C | 4025 | C | Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. | R/W | Float | 32 |
cal_coeff_A | 4028 | A | A - Probe calibration factor. | R/W | Float | 32 |
cal_coeff_B | 4029 | B | B - Probe calibration factor. | R/W | Float | 32 |
cal_coeff_C | 402A | C | C - Probe calibration factor. | R/W | Float | 32 |