Name ID Label Description Type Access Class
temp_sensor_status 403C Temp Sensor Temp Sensor - Provides status of the Temperature sensor in the TA2. Will display either OK, Shorted, or Open. R Enum 2050
flow_sensor_status 403D Flow Sensor Flow Sensor - Provides status of the Flow sensor in the TA2. Will display either OK, Shorted, or Open. R Enum 2050
probe_heater_status 403E Probe Heater Probe Heater - Provides status of the Probe Heater in the TA2. Will display either OK, Shorted, or Open. R Enum 2050
heater_setting 403F Heater Setting Heater Setting - Displays a value for the heater setting. Useful for diagnostics information. R Integer 2050
install_factor_A 4021 A Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. R/W Float 32
install_factor_B 4023 B Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. R/W Float 32
install_factor_C 4025 C Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2. R/W Float 32
cal_coeff_A 4028 A A - Probe calibration factor. R/W Float 32
cal_coeff_B 4029 B B - Probe calibration factor. R/W Float 32
cal_coeff_C 402A C C - Probe calibration factor. R/W Float 32
Name ID Label Description Type Access Class