Loading…
Name ID Label Description Type Access Class
low_flow_cutoff 1F51 Low Flow Cutoff Low Flow Cutoff - velocity values less than the entered values will not be detected. This is useful if flow is detected when a no flow condition exists. R/W Float 32
initials 40C1 Date/Time/Initials Date/Time/Initials - When and by whom calibration was performed. R/W PackedAscii 2052
MagnetrolSN 4035 Magnetrol S/N Magnetrol S/N - Serial number of this unit. R/W ASCII 2052
signal 4036 Signal Signal/PV - Displays the signal and the corresponding value of the PV. May be useful for diagnostics. R Float 2050
firmware_version 4037 Firmware Version Firmware Version - Provides the version of the Firmware and the date used by the TA2. R ASCII 2052
trim4mA 4038 4mA Trim Value 4mA Trim Value - Factory parameter, displayed for diagnostic purposes only. R Unsigned 2048
trim20mA 4039 20mA Trim Value 20mA Trim Value - Factory parameter, displayed for diagnostic purposes only. R Unsigned 2048
user_password 403A Change Password User password required to change parameter settings from keypad. R/W Unsigned 2048
delta_T 403B Delta T Delta T - Displays the set point temperature which the TA2 is controlling. Useful for diagnostics information. R Float 2050
temp_sensor_status 403C Temp Sensor Temp Sensor - Provides status of the Temperature sensor in the TA2. Will display either OK, Shorted, or Open. R Enum 2050
Name ID Label Description Type Access Class