Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pulse_mode | 4054 | Output Function | Output Function - select the operation of the transistor output. | R/W | Enum | 2048 |
pulse_units | 4055 | Pulse Units | Pulse Units - Select units of measurements used by the pulse output. | R/W | Enum | 2048 |
pulse_mult | 4056 | Pulse Multiplier | Multiplier for the pulse output. For example, for a flow rate of 200 units per second,use a multiplier of 10 to create a pulse rate of 2000 Hz. If the pulse rate is too high, a "Pulse Multiplier Error" will occur. | R/W | Enum | 2048 |
pulse_freq | 4057 | Pulse Max Freq | Pulse Maximum Frequency - Select the maximum frequency that matches the specifications of the external counter. If the actual pulse rate is higher than this value a "Pulse Multiplier Error" will occur. | R/W | Enum | 2048 |
alarm_setpoint | 4058 | Alarm Setpoint | Alarm Setpoint - Enter the PV value that corresponds to the desired alarm point. | R/W | Float | 2048 |
alarm_mode | 4059 | Alarm Operation | Alarm Operation - When set for low flow, the contacts will open when the actual flow rate is less than the setpoint. When set for high flow, the alarm contacts will open when the actual flow rate is greater than the setpoint. There is a built-in 10% hysteresis between the alarm point and the reset point. | R/W | Enum | 2048 |
low_pv_cutoff_A | 405A | Low Flow Cutoff | Low Flow Cutoff - primary variable reading below which the indicated value will be forced to zero. This is useful if a non-zero PV is indicated when a no flow condition exists. | R/W | Float | 2048 |
low_pv_cutoff_B | 405B | Low Flow Cutoff | Low Flow Cutoff - primary variable reading below which the indicated value will be forced to zero. This is useful if a non-zero PV is indicated when a no flow condition exists. | R/W | Float | 2048 |
zero_flow_sig_A | 405C | Zero Flow Signal | Zero Flow Signal - value which represents the signal at zero flow. | R/W | Float | 2048 |
zero_flow_sig_B | 405D | Zero Flow Signal | Zero Flow Signal - value which represents the signal at zero flow. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |