Name ID Label Description Type Access Class
pulse_mode 4054 Output Function Output Function - select the operation of the transistor output. R/W Enum 2048
pulse_units 4055 Pulse Units Pulse Units - Select units of measurements used by the pulse output. R/W Enum 2048
pulse_mult 4056 Pulse Multiplier Multiplier for the pulse output. For example, for a flow rate of 200 units per second,use a multiplier of 10 to create a pulse rate of 2000 Hz. If the pulse rate is too high, a "Pulse Multiplier Error" will occur. R/W Enum 2048
pulse_freq 4057 Pulse Max Freq Pulse Maximum Frequency - Select the maximum frequency that matches the specifications of the external counter. If the actual pulse rate is higher than this value a "Pulse Multiplier Error" will occur. R/W Enum 2048
alarm_setpoint 4058 Alarm Setpoint Alarm Setpoint - Enter the PV value that corresponds to the desired alarm point. R/W Float 2048
alarm_mode 4059 Alarm Operation Alarm Operation - When set for low flow, the contacts will open when the actual flow rate is less than the setpoint. When set for high flow, the alarm contacts will open when the actual flow rate is greater than the setpoint. There is a built-in 10% hysteresis between the alarm point and the reset point. R/W Enum 2048
low_pv_cutoff_A 405A Low Flow Cutoff Low Flow Cutoff - primary variable reading below which the indicated value will be forced to zero. This is useful if a non-zero PV is indicated when a no flow condition exists. R/W Float 2048
low_pv_cutoff_B 405B Low Flow Cutoff Low Flow Cutoff - primary variable reading below which the indicated value will be forced to zero. This is useful if a non-zero PV is indicated when a no flow condition exists. R/W Float 2048
zero_flow_sig_A 405C Zero Flow Signal Zero Flow Signal - value which represents the signal at zero flow. R/W Float 2048
zero_flow_sig_B 405D Zero Flow Signal Zero Flow Signal - value which represents the signal at zero flow. R/W Float 2048
Name ID Label Description Type Access Class