Loading…
Loading…
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
statusinfo_15 | 406F | IPC Ack | IPC Ack - Internal communications error; consult Factory. | 读 | 枚举 | 2050 |
TargetsMode | 4070 | Mode | Review all Targets detected by the transmitter including false targets (targets other than Level). Ensure that the proper Level target is shown then run Target Rejection routine. If reported Level is close to actual and the quality number is > 20, it is probably correct. Targets can be viewed in Level or Distance mode. | 读/写 | 枚举 | 2048 |
TargRejStatus | 400F | Status | The Target Rejection routine detects, stores, and cancels false targets to ensure detection of the proper level signal. The No False Target Rejection warning message will be displayed if this algorithm is not enabled. Do not proceed with False Target Rejection procedure until confirming Level and Quality values in Targets menu. False Target Rejection should be run with vessel at or near empty when all targets are exposed; re-run this routine if initial calibration is done with significant liquid in vessel. The false target profile will be disabled and this routine should be re-run if antenna or tank parameters are modified or when launcher is repositioned. | 读 | 枚举 | 2050 |
TargRejStatusType | 40AC | Target Rej Type | 读 | 枚举 | 2048 | |
TargRejLevel | 4145 | Targ Rej Level | Factory parameter, displayed for diagnostic purposes only. | 读 | 浮点 | 2048 |
TargRejAction_requested | 40AD | 写 | 枚举 | 4096 | ||
PeakListType_requested | 40AE | 写 | 枚举 | 4096 | ||
PeakList_number_of_PTP_peaks | 40AF | 读 | 无符号 | 4096 | ||
PTP_Peak1Quality | 40B0 | 读 | 无符号 | 4096 | ||
PTP_Peak2Quality | 40B1 | 读 | 无符号 | 4096 | ||
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |