Loading…
Name ID Label Description Type Access Class
diaginfo_1 4051 MultiEcho Dbl R Enum 2050
diaginfo_2 4052 Tank Dim Invld Tank Dimensions Invalid - Tank dimensions exceed maximum range of the transmitter; reduce tank height and/or Sensor Offset values. R Enum 2050
diaginfo_3 4053 Info 0008 R Enum 2050
diaginfo_4 4054 Info 0010 R Enum 2050
diaginfo_5 4055 Incmp Targ Rej Incomplete Target Rejection - False target only partially captured; re-run False Target Rejection routine. R Enum 2050
diaginfo_6 4056 Scatter Target Scattered Target - Return signals scattered due to turbulence in vessel. R Enum 2050
diaginfo_7 4057 Uncertn Target Uncertain Target - Target is missing, but not determined to be lost; device is holding last valid value while confirming the target position, will continue based upon the LOE Delay value, consult Factory if problem persists. R Enum 2050
diaginfo_8 4058 DC Noise DC Noise - Excessive noise on A/D channel; consult Factory. R Enum 2050
diaginfo_9 4059 Signal Too Hi Signal Too High - Level signal amplitude is excessive; choose higher Dielectric range, reduce Turbulence or Foam settings, consult Factory if problem persists. R Enum 2050
diaginfo_10 405A Signal Too Low Signal Too Low - Level signal amplitude is insufficient; choose lower Dielectric range, increase Turbulence or Foam settings, consult Factory if problem persists. R Enum 2050
Name ID Label Description Type Access Class