Name ID Label Description Type Access Class
diag17_text 4860 High Volume Alarm Volume calculated from Level reading exceeds capacity of vessel or Custom Table. Check settings: Vessel Dimensions, Custom Table entries. R/W Enum 4096
diag18_text 4861 Spare Indicator 5 R/W Enum 4096
diag19_text 4862 Initializing Distance measurement is inaccurate while internal filters are settling. Wait for up to 10 seconds. R/W Enum 4096
diag20_text 4863 Config Changed A parameter has been modified from the User Interface. If desired, reset Config Changed indicator in ADVANCED CONFIG. R/W Enum 4096
diag21_text 4864 Spare Indicator 6 R/W Enum 4096
diag22_text 4865 Ramp Slope Error Internal signal timing out of limits causing inaccurate distance measurement. Check accuracy of Distance reading. Replace transmitter electronics. R/W Enum 4096
diag23_text 4866 High Elec Temp Electronics too hot. May compromise Distance measurement or damage instrument. Shield transmitter from heat source or increase air circulation. Locate transmitter remotely in a cooler area. R/W Enum 4096
diag24_text 4867 Low Elec Temp Electronics too cold. May compromise Distance measurement or damage instrument. Insulate transmitter. Locate transmitter remotely in a warmer area. R/W Enum 4096
diag25_text 4868 Calibration Req'd Factory calibration has been lost. Measurement accuracy is diminished. Return transmitter to factory for recalibration. R/W Enum 4096
diag26_text 4869 Reject Curve Invalid Echo Rejection invalid. May report erroneous Level readings. Upr Echo may be lost near the top of the vessel. Save a fresh Echo Rejection Curve. R/W Enum 4096