Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
diag7_text | 4856 | Spare Indicator 1 | R/W | Enum | 4096 | |
diag8_text | 4857 | Analog Board Error | Unrecoverable hardware failure. Contact Technical Support. | R/W | Enum | 4096 |
diag9_text | 4858 | Spare Indicator 2 | R/W | Enum | 4096 | |
diag10_text | 4859 | Spare Indicator 3 | R/W | Enum | 4096 | |
diag11_text | 485A | No Fiducial | The fiducial pulse is not located where expected, or the fiducial amplitude is not in the expected range. Increase Fiducial Gain. Adjust Window to result in Fiducial Ticks of 100 - 300. Contact Technical Support. | R/W | Enum | 4096 |
diag12_text | 485B | Too Many Echoes | Excessive number of possible echoes detected. Check settings: Dielectric Range, Sensitivity, polarization direction. View Echo Curve Contact Technical Support. | R/W | Enum | 4096 |
diag13_text | 485C | Safety Zone Alarm | Risk of echo loss if liquid rises above Top Blocking Distance. Ensure that liquid cannot reach Top Blocking Distance. | R/W | Enum | 4096 |
diag14_text | 485D | Echo Lost | No detectable level signal identified within the configured range. Check settings: Dielectric Range, Sensitivity, Tank Height Increase Sensitivity. View Echo Curve. | R/W | Enum | 4096 |
diag15_text | 485E | Spare Indicator 4 | R/W | Enum | 4096 | |
diag16_text | 485F | Config Conflict | Selections of Measurement Type and Primary Variable (PV) are incompatible. Change Measurement Type and/or PV to appropriate settings. | R/W | Enum | 4096 |