Name ID Label Description Type Access Class
trend_volume_value 409F Volume Volume of product in the vessel. R Float 0
trend_head_value 409D Head Height of liquid in a flume or weir. R Float 0
trend_flow_value 40A0 Flow Flow R Float 0
trend_distance_value 409E Distance Distance measured from the sensor reference point downward to the surface of the material in the vessel. R Float 0
trend_analog_output_value 40A3 Loop current Loop Current - loop current value as perceived by the device. R Float 0
trend_percent_output_value 40A4 PV % Range Percent of Range - Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 0
trend_echo_str_value 40A1 Echo Strength Relative strength of the level signal being detected (0-100). Review Echo Curve to ensure transmitter is detecting correct target. R Unsigned 0
trend_echo_margin_value 40A2 Echo Margin Echo Margin is a numeric value that is related to the strength of the target peak relative to the Level Threshold or competing waveform features, i.e. "noise." Review Echo Curve. Run Echo Rejection if a small, false echo exists above the Level echo. Echo Margin will increase. Echo Margin values should be >20. R Unsigned 0
datalog_event1_enable 40E8 Level R/W Enum 0
datalog_event2_enable 40EA Distance R/W Enum 0
Name ID Label Description Type Access Class