Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
ProbeModel | 4010 | Probe Model | Type of probe connected to transmitter | R/W | Enum | 2048 |
ProbeMount | 4011 | Probe Mount | Mounting style of probe fitting | R/W | Enum | 2048 |
ProbeLength | 4012 | Probe Length | Distance from face of process seal to end of probe | R/W | Float | 2048 |
Offset | 4013 | Probe Offset | Desired level reading when liquid surface is at end of probe | R/W | Float | 2048 |
UprDielectric | 4014 | Upper Dielectric | Dielectric constant of upper liquid in vessel | R/W | Float | 2048 |
Set4mA | 400E | 4mA Set Point | Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions | R/W | Float | 64 |
Set20mA | 400D | 20mA Set Point | Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions | R/W | Float | 64 |
Fault | 400A | Fault State | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 65 |
Initials | 4015 | Date/Time/Initials | When and by whom calibration was performed | R/W | PackedAscii | 2052 |
EnteredPassword | 4016 | Enter Password | Password is required for adjusting Advanced Setup parameters Magnetrol S/N and Device id, and Factory Settings parameters Window, Range, Ifc Gain, Upr Gain, Conversion Factor and Scale Offset | W | Unsigned | 2052 |
Name | ID | Label | Description | Type | Access | Class |