Name ID Label Description Type Access Class
ProbeModel 4010 Probe Model Type of probe connected to transmitter R/W Enum 2048
ProbeMount 4011 Probe Mount Mounting style of probe fitting R/W Enum 2048
ProbeLength 4012 Probe Length Distance from face of process seal to end of probe R/W Float 2048
Offset 4013 Probe Offset Desired level reading when liquid surface is at end of probe R/W Float 2048
UprDielectric 4014 Upper Dielectric Dielectric constant of upper liquid in vessel R/W Float 2048
Set4mA 400E 4mA Set Point Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Set20mA 400D 20mA Set Point Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Fault 400A Fault State Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 65
Initials 4015 Date/Time/Initials When and by whom calibration was performed R/W PackedAscii 2052
EnteredPassword 4016 Enter Password Password is required for adjusting Advanced Setup parameters Magnetrol S/N and Device id, and Factory Settings parameters Window, Range, Ifc Gain, Upr Gain, Conversion Factor and Scale Offset W Unsigned 2052