Name ID Label Description Type Access Class
diag28_text 4921 Ramp Interval Error Internal signal timing out of limits causing inaccurate distance measurement. Check accuracy of Distance reading. Replace transmitter electronics. R/W Enum 4096
diag29_text 4922 High Elec Temp Electronics too hot. May compromise Distance measurement or damage instrument. Shield transmitter from heat source or increase air circulation. Locate transmitter remotely in a cooler area. R/W Enum 4096
diag30_text 4923 Low Elec Temp Electronics too cold. May compromise Distance measurement or damage instrument. Insulate transmitter. Locate transmitter remotely in a warmer area. R/W Enum 4096
diag31_text 4924 Calibration Req'd Factory calibration has been lost. Measurement accuracy is diminished. Return transmitter to factory for recalibration. R/W Enum 4096
diag32_text 4925 Echo Reject Invalid Echo Rejection inoperative. May report erroneous Level readings. Upr Echo may be lost near top of probe. Save a fresh Echo Rejection Curve. R/W Enum 4096
diag33_text 4926 Spare Indicator 7 R/W Enum 4096
diag34_text 4927 Inferred Level Distance measurement calculated indirectly from probe elongation. Level reading is only approximate. Verify Level reading. If incorrect, compare Dielectric Range against EoP Dielectric reading. R/W Enum 4096
diag35_text 4928 Adjust Analog Outpt Loop current is inaccurate. Perform TRIM LOOP maintenance procedure. R/W Enum 4096
diag36_text 4929 Totalizer Data Lost Non-volatile Totalizer Data storage failing. Contact Technical Support. R/W Enum 4096
diag37_text 492A No Probe Target Automatic vapor compensation is not operational either because liquid level is too high or probe has no target. Check settings: Probe Model, Assure that liquid level remains well below target. Consult I&O manual for limits. R/W Enum 4096
Name ID Label Description Type Access Class