Name ID Label Description Type Access Class
diag18_text 4917 Config Conflict Selections of Measurement Type and PV are incompatible. Change Measurement Type and/or PV to appropriate settings. R/W Enum 4096
diag19_text 4918 High Volume Alarm Volume calculated from Level reading exceeds capacity of vessel or custom table. Check settings: Vessel Dimensions, Custom Table entries. R/W Enum 4096
diag20_text 4919 High Flow Alarm Flow calculated from Distance reading exceeds capacity of flow element or custom table. Check settings: Flow Element, Gen Eqn Factors, Custom Table entries. R/W Enum 4096
diag21_text 491A Spare Indicator 3 R/W Enum 4096
diag22_text 491B Initializing Distance measurement is inaccurate while internal filters are settling. Wait for up to 10 seconds. R/W Enum 4096
diag23_text 491C Analog Output Fixed Loop current not following PV. May be caused by existing alarm condition, ongoing Loop test or Trim Loop operations. If unexpected, check setting: Loop Current Mode. Ensure not in Loop Test. R/W Enum 4096
diag24_text 491D Config Changed A parameter has been modified from the User Interface. If desired, reset Config Changed indicator in ADVANCED CONFIG. R/W Enum 4096
diag25_text 491E Spare Indicator 4 R/W Enum 4096
diag26_text 491F Spare Indicator 5 R/W Enum 4096
diag27_text 4920 Spare Indicator 6 R/W Enum 4096