Name ID Label Description Type Access Class
diag8_text 490D Default Parameters All saved parameters are set to default values. Perform complete Device Setup. R/W Enum 4096
diag9_text 490E No Probe No probe connected. Attach a probe. Torque HF nut. Clean gold pin on transmitter and socket on probe. R/W Enum 4096
diag10_text 490F No Fiducial Reference signal too weak to detect. Torque HF nut. Clean gold pin on transmitter and socket on probe. Check settings: Fiducial Gain, HF Cable Length, Window. Increase Fid Gain. R/W Enum 4096
diag11_text 4910 No Echoes No signal detected anywhere on probe. Check settings: Dielectric Range, Sensitivity, EoP Thresh Value. Increase Sensitivity. Lower EoP Thresh. View Echo Curve. R/W Enum 4096
diag12_text 4911 Echo Lost Signal from the liquid too weak to detect. Check settings: Upr Dielectric, Blocking Distance, Sensitivity. Increase Sensitivity. View Echo Curve. R/W Enum 4096
diag13_text 4912 Spare Indicator 2 R/W Enum 4096
diag14_text 4913 EoP Above PrbeEnd End of Probe appears above Probe Length. Check settings: Probe Length. Decrease Sensitivity. Increase Blocking Distance. View Echo Curve. R/W Enum 4096
diag15_text 4914 Lvl Below PrbeEnd Level signal appears beyond Probe Length. (Possible water bottom situation). Check settings: Probe Model, Probe Length, Level Threshold = Fixed. Increase Sensitivity. View Echo Curve. R/W Enum 4096
diag16_text 4915 EoP Below PrbeEnd End of Probe appears beyond Probe Length. Check settings: Probe Length, Dielectric Range. Increase Sensitivity. View Echo Curve. R/W Enum 4096
diag17_text 4916 Safety Zone Alarm Risk of echo loss if liquid rises above Blocking Distance. Ensure that liquid cannot reach Blocking Distance. R/W Enum 4096