Name ID Label Description Type Access Class
FidThreshValue 47D3 Fid Thresh Value Threshold for detecting fiducial. Default setting is suitable for most installations. Refer to I & O manual before adjusting. R/W Unsigned 2048
EOP_Analysis 47D4 EoP Analysis Optional measurement mode which allows for liquid level to be inferred based on position of the End-of-Probe Signal. (Should only be invoked after contacting Technical Support). R/W Enum 2048
EOP_Polarity 47D5 EoP Polarity Specifies whether positive-going or negative-going signals are to be used as the End-of-Probe (EOP). Contact Technical Support for assistance. R/W Enum 2048
EOP_Dielectric 47D6 EoP Dielectric Allows for manual entry of the material dielectric constant based on End of Probe position. (Range is 1.2 - 1.4). Contact Technical Support for assistance. R/W Float 2048
EOP_Distance 47D7 EoP Distance The measured distance from the sensor reference point to the end of probe. R Float 2050
EOP_Apparent_Diel 47D8 EoP Measured Diel The product dielectric constant as calculated by the transmitter based on the end of probe location. (Displayed for diagnostic purposes only.) R Float 2050
fixed_loop_current_value 47D9 Fixed Loop Current Parameter used to set the value of the fixed output current. R/W Float 2048
vessel_type 47DA Vessel Type Shape of vessel. (Used when Measurement Type = Volume.) R/W Enum 2048
radius 47DB Radius Radius of the cylindrical/spherical portion of the vessel. R/W Float 2048
ellipse_depth 47DC Ellipse Depth Depth of the elliptical portion of the vessel. R/W Float 2048
Name ID Label Description Type Access Class