Name ID Label Description Type Access Class
MinTemp 403B Min Temperature Minimum temperature measured in the electronics compartment. R Integer 2051
SZFault 403C SZ Fault State Safety Zone Fault State defines how the Analog Output will respond when the transmitter detects a level within the Safety Zone. Enable fault to ensure safe, reliable high-level readings in critical applications. If Latch 3.6 or Latch 22 is chosen, the unit will remain in alarm until it is manually cleared with the SZ Alarm Reset. R/W Enum 65
SZHeight 403D SZ Height Safety Zone Height - Enter a distance that defines a safety zone just below the Blocking Distance. If Safety Zone Fault is enabled, the transmitter will report a fault if the level rises into this zone. R/W Float 2048
SZHysteresis 403E SZ Hysteresis Level must fall this distance below Safety Zone to clear a Safety Zone Fault. Default setting is suitable for most installations. Refer to I & O manual before adjusting. R/W Float 2048
SteamFactor 403F Derating Factor Displayed for diagnostic purposes only. R Integer 10
TargOperMode 4040 Target Oper Mode Run mode enables automatic compensation. Cal mode allows calibration of target through air; Off mode disables automatic compensation. Default setting is suitable for most installations. Refer to I & O manual before adjusting. R/W Enum 8
TargetCalValue 4041 Targ Calib Value Factory parameter, displayed for diagnostic purposes only. R/W Integer 8
TargetTicks 4042 Target Ticks Displayed for diagnostic purposes only. R Integer 10
TargetAmpl 4043 Target Amplitude Displayed for diagnostic purposes only. R Unsigned 10
Factory_Param1 4044 HF Cable Remote HF Cable distance. Consult factory for assistance. R/W Integer 8