Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
EnteredPassword | 401D | Enter Password | Certain parameters are password protected to prevent access by the user. Parameters that should never be changed by the user are protected with the Factory password. Some parameters intended for field use that may be changed in special, controlled situations require the Superuser password. | W | Unsigned | 2052 |
FiducialType | 401E | Fiducial Type | Fiducial Type can be used to override the default fiducial detection mode for some probe models. Default setting is suitable for most installations. Refer to I & O manual before adjusting. | R/W | Enum | 2048 |
Threshold | 401F | Threshold | Selects the negative signal threshold control for measuring the upper level pulse. Use 'CFD' except in situation with low dielectric (< 3) material over higher dielectric (> 10) material, e.g., water bottom or interface measurement, in which case use 'Fixed'. | R/W | Enum | 2048 |
Window | 4020 | Window | Factory parameter, displayed for diagnostic purposes only. | R/W | Unsigned | 2048 |
Fid_Gain | 4021 | Fiducial Gain | Default setting is suitable for most installations. Refer to I & O manual before adjusting. | R/W | Unsigned | 2048 |
Sensitivity | 4022 | Sensitivity | Sensitivity of instrument to surface of material in vessel. Default setting is suitable for most installations. Refer to I & O manual before adjusting. | R/W | Unsigned | 2048 |
Trim4mA | 4023 | 4mA Trim Value | Displayed for diagnostic purposes only. | R | Unsigned | 2051 |
Trim20mA | 4024 | 20mA Trim Value | Displayed for diagnostic purposes only. | R | Unsigned | 2051 |
MagnetrolSSN | 4025 | Magnetrol S/N | Magnetrol S/N - Serial number of this unit. | R/W | ASCII | 2052 |
Initials | 4026 | Date/Time/Initials | When and by whom calibration was performed. | R/W | PackedAscii | 2052 |
Name | ID | Label | Description | Type | Access | Class |