Name ID Label Description Type Access Class
ProbeType 400A Probe Type Type of probe connected to transmitter R/W Enum 2048
ProbeMount 400B Probe Mount Mounting style of probe fitting R/W Enum 2048
ProbeLength 400C Probe Length Distance from face of process seal to end of probe R/W Float 2048
Offset 400D Probe Offset Desired level reading when liquid surface is at end of probe R/W Float 2048
Dielectric1 400E Dielectric Dielectric constant of material in vessel. If unknown, use 'Varies'. R/W Enum 2048
Set4mA 400F 4mA Set Point Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Set20mA 4010 20mA Set Point Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Fault 4011 Fault State Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 65
Initials 4012 Date/Time/Initials When and by whom calibration was performed R/W PackedAscii 2052
EnteredPassword 4013 Enter Password Password is required for adjusting Advanced Setup parameters Magnetrol S/N and Device id, and Diagnostic-Digital Settings parameters Window, Range, Gain, Conversion Factor and Scale Offset W Unsigned 2052