Name ID Label Description Type Access Class
ProbeLength 400F Probe Length Distance from face of process seal to end of probe R/W Float 2048
ProbeOffset 4010 Probe Offset Desired level reading when liquid surface is at end of probe R/W Float 2048
LevelTrim 4011 Level Trim Fixed amount added to measurement to adjust level reading R/W Float 2048
SensitivityDielectric 4012 R/W Enum 2048
Set4mA 400D 4mA Set Point Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Set20mA 400C 20mA Set Point Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R/W Float 64
Fault 4009 Fault State Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 65
Deadband 4013 Deadband Distance along probe where instrument begins sensing level of material in vessel. Default setting suitable for most installations. Refer to I & O manual before adjusting. R/W Float 2048
Threshold 4014 Threshold Use 'CFD' except in situation with low dielectric (< 10) material over high dielectric (> 10), e.g. oil over water R/W Enum 2048
Initials 4015 Date/Time/Initials When and by whom calibration was performed R/W PackedAscii 2052
Name ID Label Description Type Access Class