Loading…
Name ID Label Description Type Access Class
lvl_set20mA 4015 20mA Set Point Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 64
density_set4mA 4016 4mA Set Point Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 64
density_set20mA 4017 20mA Set Point Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 64
sensor_serial_number 4018 Snsr s/n R Unsigned 2048
span_pct 4000 Percent of Span W Float 4096
MeasType 4002 Measurement Type Measurement Type determines the process variable that controls the loop. R/W Enum 2048
ModelNumber 4019 Model Number Model Number of device. R/W Enum 2048
DisplacerLength 401A Displacer Length Level range of displacer. R/W Float 2048
DisplacerDiameter 401B Displacer Diameter Diameter of displacer. R/W Float 2048
DisplacerWeight 401C Displacer Weight Weight of displacer. R/W Float 2048
Name ID Label Description Type Access Class