Name ID Label Description Type Access Class
temperatureSimulated 403B Simulate W Enum 2052
KP 403D KP PID parameter. KP is the proportional gain. R/W Unsigned 2048
KI 403E KI PID parmeter. KI is the integral constant. R/W Unsigned 2048
KD 403F KD PID parmeter. KD is the differential constant. R/W Unsigned 2048
KP_ 4040 KP_ PID parmeter. KP_ is a multiplier of KP. When the deviation is within 1%, will be enabled. Standard value is 10, which means 100%. R/W Unsigned 2048
KI_ 4041 KI_ PID parmeter. KI_ is a multiplier of KI. When the deviation is within 1%, will be enabled. Standard value is 10, which means 100%. R/W Unsigned 2048
KD_ 4042 KD_ PID parmeter. KD_ is a multiplier of KD. When the deviation is within 1%, will be enabled. Standard value is 10, which means 100%. R/W Unsigned 2048
actuatorDir 4043 Actuator Direction Actuator Direction. Sets the direction of operation of the actuator. R/W Enum 2048
valveDir 4044 Valve Direction Valve Direction. R/W Enum 2048
positionDir 4045 Positioner Direction Positioner Direction. Sets the direction of the operation of the positioner. In the Normal setting, the signal increased, increasing the output air pressure. R/W Enum 2048
Name ID Label Description Type Access Class