Name ID Label Description Type Access Class
input_percent_range 401C PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
input_transfer_function 401D Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R/W Enum 32
input_units 401E PV rnge unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 32
input_upper_value 401F PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
input_lower_value 4020 PV LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
sensor_serial_number 4007 PV Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
sensor_type 400F Snsr Type Sensor Type- Kind of sensor(s) connected at this time R/W Enum 32
sensor_wires 4010 Snsr Wires Sensor Connection- Technique used to connect the sensor to the Field Device R/W Enum 32
cjc_mode 4013 CJ Comp. CJ Compensation Mode Switch - Cold Junction Compensation Mode which becomes effective at Thermcouple input sensor R/W Enum 32
burnout_mode 400E Burnout Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 32
Name ID Label Description Type Access Class