Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
utpPressure | 40F8 | Update Time | Update Time Period 'UTP'. Indicates the maximum period between updates of the process variable. | R | Time | 8 |
simulatePressure | 40F9 | Set Simulation | Desired setting of the process variable simulation. If enabled, the process variable will be simulated and won't show the actual process value. | W | Enum | 2048 |
propertiesPressure | 40FA | Properties | Properties, indicate e.g. the simulation state. | R | BitEnum | 10 |
dunDensity | 40FC | Unit Density | Unit for density. | R/W | Enum | 8 |
dfoOperatingDensity | 40FE | Format Density | Display format for operating density. Local for HART applications, no correlation with device's local display. | R/W | Enum | 4096 |
dvlOperatingDensity | 40FD | Density | Operating density process variable | R/W | Float | 10 |
uslOperatingDensity | 40FF | Upper Sensor Limit | Valore limite sensore superiore - Definisce il valore massimo utilizzabile per il valore di campo superiore. | R | Float | 8 |
lslOperatingDensity | 4100 | Lower Sensor Limit | Valore limite sensore inferiore - Definisce il valore minimo utilizzabile per il valore di campo inferiore. | R | Float | 8 |
mspOperatingDensity | 4101 | Minimum Span | Valore intervallo minimo - Definisce la differenza più piccola consentita tra il valore di campo superiore e il valore di campo inferiore. | R | Float | 8 |
clsOperatingDensity | 4102 | Class | Device Variable Class | R | Enum | 8 |
Name | ID | Label | Description | Type | Access | Class |