Loading…
Name ID Label Description Type Access Class
pcrQv 413B QV % range Percent of range; tracks the associated measured value with respect to the range defined by the Lower Range Value and Upper Range Value. Current/frequency output B if available (Modular IO / Exi IO). R Float 34
tfcQv 413C Xfer fnctn R Enum 32
urvQv 413D URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
lrvQv 413E LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
aunQv 4145 AO unit R Enum 64
avlQv 4144 QV Output Value Analog output value that tracks the associated measured value. Current/frequency output B. R/W Float 66
acdQv 4146 AO Alrm typ R Enum 64
uepQv 4147 AO hi end pt Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
lepQv 4148 AO lo end pt Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
adpQv 4149 Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R Float 64
Name ID Label Description Type Access Class