Loading…
Name ID Label Description Type Access Class
urvSv 4119 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
lrvSv 411A LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
aunSv 4121 AO unit R Enum 64
avlSv 4120 SV Output Value Analog output value that tracks the associated measured value. Frequency output D if available. R/W Float 66
acdSv 4122 AO Alrm typ R Enum 64
uepSv 4123 AO hi end pt Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
lepSv 4124 AO lo end pt Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
adpSv 4125 Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R Float 64
acfSv 4126 Channel flags Analog Channel Flags- Defines the characteristics of the Analog Channel R BitEnum 64
pcrTv 4129 TV % range Percent of range; tracks the associated measured value with respect to the range defined by the Lower Range Value and Upper Range Value. Current/frequency output A if available (Modular IO / Exi IO). R Float 34
Name ID Label Description Type Access Class