Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
dummy | 414A | R/W | Float | 2048 | ||
tracing_velocity | 4149 | Tracking Velocity | This function defines the maximum rate of change of the level that can occur in operation. The measured value of the device cannot change at a faster rate than the tracking velocity. | R/W | Float | 0 |
epsilon_r_gas | 4147 | Epsilon R gas | This parameter corresponds to the dielectric constant of the gas which is situated between the flange face and the product. In most applications, this parameter should not be changed (dielectric ambient air = 1,0). | R/W | Float | 0 |
epsilon_r_product | 4148 | Epsilon R Product | For applications with low dielectric constant. The most accurate value possible must be typed into this parameter. | R/W | Float | 0 |
measure_threshold | 4145 | Level Threshold | This corresponds to the level threshold of the signal amplitude. If the signal goes beyond this threshold, it is measured. Otherwise, it is ignored. | R/W | Float | 0 |
probeEnd_threshold | 4146 | Probe End Threshold | This corresponds to the probe end threshold. If the signal goes beyond this threshold, it is measured. Otherwise, it is ignored. | R/W | Float | 0 |
DielctProductMini | 414B | Epsilon R Product mini. | R/W | Float | 0 | |
DielctProductMaxi | 414C | Epsilon R Product maxi. | R/W | Float | 0 | |
user_code_1 | 414E | Code 1 | W | Unsigned | 2052 | |
user_code_2 | 414F | Code 1 | W | Unsigned | 2052 | |
Name | ID | Label | Description | Type | Access | Class |