Name ID Label Description Type Access Class
MRV 4055 PV MRV Medium range value for Split ranging loop control mode R/W Float 32
sensor1_bias 4056 Sensor1 Bias R/W Float 8
sensor2_bias 4057 Sensor2 Bias R/W Float 8
break_detect_mode 4058 Break Detect Select either sensor break detection or no sensor break detection. R/W Enum 64
cj_selection 4059 CJ Selection Select either external or internal cold junction compensation. R/W Enum 8
match_pvs 405D Match PV If you set this function ON, Sensor2 will be matched to Sensor1. R/W Enum 34
latching_mode 405E Latching Alarm Select the latching configuration. R/W Enum 64
fixed_cj_value 405F Fixed CJ Compensation Value Fixed CJ Compensation Value R/W Float 10
loop_control_choice 4002 Loop Control Mode Select the loop control mode: 1.Averaging: The loop control method will be (Sensor1+Sensor2)/2. 2.Differential: The loop control method will be (Sensor1-Sensor2). 3.Sensor1: The loop current will be dependent on Sensor1 solely. 4.Sensor2: The loop current will be dependent on Sensor2 solely. 5.Redundant: If Sensor1 input fails, loop current is controlled by Sensor2 input. 6.Split Ranging: The range of both sensors will be split into 2 ranges. Range 1 will be controlled by Sensor1 and Range 2 will be controlled by Sensor2. R/W Enum 10
controlling_var 405A Loop Controlled By Currently loop current is controlled by the shown variable. This is dependent on the sensor 1 and 2 inputs. R Enum 10